| Assessment Year | 2002 |
|---|---|
| Principal Product | Corrugated Containers |
| NAICS |
n/a
|
| SIC | 2653: Corrugated and Solid Fiber Boxes |
| Sales Range | $50 M to 100M |
| # of Employees | 210 |
| Plant Area |
400,000
ft2
|
| Annual Production | 81,000
ton
|
| Production Hrs. Annual | 6,000
hrs
|
| Location (State) | Louisiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $821,939 | 10,772,000 |
kWh
|
$0.076 |
| Electricity Demand | $63,136 | 21,548 |
kW-mo/yr
|
$2.93 |
| Electricity Fees | $32,877 | - |
|
- |
| Natural Gas | $699,873 | 111,523 |
MMBtu
|
$6.28 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $68,632 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $14,438 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.2414: Use waste heat from hot flue gases to preheat | $36,202 | $24,480 | - | - | - |
$36,202
-
MMBtu
|
|
| 02 | 2.7134: Use photocell controls | $17,992 | $946 |
$15,521
202,464
kWh
|
$1,779
-
kW-mo/yr
|
$692 | - | |
| 03 | 2.2511: Insulate bare equipment | $6,380 | $4,526 | - | - | - |
$6,380
-
MMBtu
|
|
| 04 | 2.2135: Repair and eliminate steam leaks | $6,088 | $900 | - | - | - |
$6,088
-
MMBtu
|
|
| 05 | 2.3212: Optimize plant power factor | $1,970 | $6,440 | - |
$1,894
-
kW-mo/yr
|
$76 | - | |
| TOTAL RECOMMENDED | $68,632 | $37,292 |
$15,521
202,464
kWh
|
$3,673
-
kW-mo/yr
|
$768 |
$48,670
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $14,438 | $11,866 | - |
$1,894
-
kW-mo/yr
|
$76 |
$12,468
-
MMBtu
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs