Assessment Year | 2001 |
---|---|
Principal Product | General Machining and Contract Manufacturing |
NAICS |
n/a
|
SIC | 3312: Steel Works, Blast Furnaces (Including Coke Ovens), and Rolling Mills |
Sales Range | $10 M to 50M |
# of Employees | 135 |
Plant Area |
80,000
ft2
|
Annual Production | 60,000
pieces
|
Production Hrs. Annual | 5,616
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $242,094 | 4,279,000 |
kWh
|
$0.057 |
Electricity Demand | $109,315 | 19,451 |
kW-mo/yr
|
$5.62 |
Electricity Fees | $14,056 | - |
|
- |
Natural Gas | $132 | 12 |
MMBtu
|
$11.00 |
Other Gas | $4,795 | 595 |
MMBtu
|
$8.06 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $49,707 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $23,422 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | LPG Savings | Other Gas Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,494 | $1,440 |
$4,321
76,363
kWh
|
- | $173 | - | - | - | |
02 | 2.1335: Replace gasoline with diesel, lpg, or natural gas | $2,754 | $1,480 | - | - | $105 |
$(-2,146.0)
-
MMBtu
|
$4,795
-
MMBtu
|
- | |
03 | 2.8114: Change rate schedules or other changes in utility service | $6,478 | $1,000 | - | - | - | - | - | $6,478 | |
04 | 2.2511: Insulate bare equipment | $16,464 | $3,385 |
$15,831
279,800
kWh
|
- | $633 | - | - | - | |
05 | 2.7111: Reduce illumination to minimum necessary levels | $2,464 | - |
$1,874
33,116
kWh
|
$495
-
kW-mo/yr
|
$95 | - | - | - | |
06 | 2.3212: Optimize plant power factor | $17,053 | $23,870 | - |
$16,397
-
kW-mo/yr
|
$656 | - | - | - | |
TOTAL RECOMMENDED | $49,707 | $31,175 |
$22,026
389,279
kWh
|
$16,892
-
kW-mo/yr
|
$1,662 |
$(-2,146.0)
-
MMBtu
|
$4,795
-
MMBtu
|
$6,478 | ||
TOTAL IMPLEMENTED | $23,422 | $4,825 |
$22,026
389,279
kWh
|
$495
-
kW-mo/yr
|
$901 | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | LPG Savings | Other Gas Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs