Assessment Year | 2025 |
---|---|
Principal Product | Army Equipments |
NAICS | 336992: Military Armored Vehicle, Tank, and Tank Component Manufacturing |
SIC | 3711: Motor Vehicles and Passenger Car Bodies |
Sales Range | $1 M to 5M |
# of Employees | 5,600 |
Plant Area |
4,200,000
ft2
|
Annual Production | 1,000
units
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $4,472,065 | 66,243,000 |
kWh
|
$0.068 | |
Electricity Demand | $223,590 | 133,748 |
kW-mo/yr
|
$1.67 | |
Electricity Fees | $1,362,522 | - |
|
- | |
Natural Gas | $661,623 | 201,786 |
MMBtu
|
$3.28 | |
Waste Disposal Costs | |||||
Water Usage | $218,412 | 36,402 |
Tgal
|
$6.00 | |
Water Disposal | $215,332 | 33,128 |
Tgal
|
$6.50 | |
TOTAL YEARLY COSTS | $7,153,544 | ||||
RECOMMENDED SAVINGS* | $3,254,758 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $32,559 | $6,000 |
$31,496
463,182
kWh
|
$1,063
-
kW-mo/yr
|
- | - | |
02 | 2.7135: Install occupancy sensors | $37,915 | $27,000 |
$37,915
557,574
kWh
|
- | - | - | |
03 | 3.2173: Convert to robotic painting | $218,856 | $362,095 |
$18,317
269,372
kWh
|
$539
-
kW-mo/yr
|
- | $200,000 | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $302,215 | $689,368 |
$292,195
4,296,985
kWh
|
$10,020
-
kW-mo/yr
|
- | - | |
05 | 2.7233: Use properly designed and sized hvac equipment | $456,991 | $909,175 |
$449,401
6,608,833
kWh
|
$2,527
-
kW-mo/yr
|
$5,063
-
MMBtu
|
- | |
06 | 2.2523: Reduce infiltration to refrigerated areas; isolate hot equipment from refrigerated areas | $11,873 | $25,113 |
$5,388
79,248
kWh
|
$(-295.0)
-
kW-mo/yr
|
$6,780
-
MMBtu
|
- | |
07 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $2,194,349 | $9,580,000 |
$2,570,400
37,800,000
kWh
|
$90,180
-
kW-mo/yr
|
$(-466,231.0)
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $3,254,758 | $11,598,751 |
$3,405,112
50,075,194
kWh
|
$104,034
-
kW-mo/yr
|
$(-454,388.0)
-
MMBtu
|
$200,000 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs