Assessment Year | 2024 |
---|---|
Principal Product | Fiber Optical Connectors |
NAICS | 334417: Electronic Connector Manufacturing |
SIC | 3678: Electronic Connectors |
Sales Range | $10 M to 50M |
# of Employees | 80 |
Plant Area |
90,000
ft2
|
Annual Production | 100,000
pieces
|
Production Hrs. Annual | 2,340
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $286,822 | 4,975,229 |
kWh
|
$0.058 |
Electricity Demand | $83,828 | 11,002 |
kW-mo/yr
|
$7.62 |
Electricity Fees | $5,914 | - |
|
- |
Natural Gas | $675 | 53 |
MMBtu
|
$12.80 |
TOTAL YEARLY COSTS | $377,239 | |||
RECOMMENDED SAVINGS* | $88,202 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7261: Install timers and/or thermostats | $36,732 | $3,600 |
$36,732
633,303
kWh
|
- | - | - | |
02 | 2.7135: Install occupancy sensors | $1,709 | $3,000 |
$1,709
29,465
kWh
|
- | - | - | |
03 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $44,903 | $88,000 |
$109,064
1,880,424
kWh
|
- |
$(-91,251.0)
-
MMBtu
|
$27,090 | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,858 | $32,631 |
$3,250
56,035
kWh
|
$1,608
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $88,202 | $127,231 |
$150,755
2,599,227
kWh
|
$1,608
-
kW-mo/yr
|
$(-91,251.0)
-
MMBtu
|
$27,090 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs