Assessment Year 2022
Principal Product SHIPS
NAICS 336611: Ship Building and Repairing
SIC 3731: Ship Building and Repairing
Sales Range $100
M
to 500
M
# of Employees 600
Plant Area 2,000,000
ft2
Annual Production 3
pieces
Production Hrs. Annual 8,736
hrs
Location (State) Pennsylvania

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,956,196 18,840,339
kWh
Electricity Demand $64,975 48,116
kW-mo/yr
Electricity Fees $5,718 -
TOTAL YEARLY COSTS $2,026,889
RECOMMENDED SAVINGS* $691,537 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $130,874 $22,000 $124,590
1,197,988
kWh
$6,284
-
kW-mo/yr
02 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $84,178 $47,500 $78,314
753,021
kWh
$5,864
-
kW-mo/yr
03 2.7142: Utilize higher efficiency lamps and/or ballasts $330,596 $199,875 $324,805
3,123,120
kWh
$5,791
-
kW-mo/yr
04 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $49,409 $33,000 $48,546
466,792
kWh
$863
-
kW-mo/yr
05 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $8,036 $10,414 $7,746
74,481
kWh
$290
-
kW-mo/yr
06 2.7232: Replace existing hvac unit with high efficiency model $88,444 $135,000 $87,818
844,405
kWh
$626
-
kW-mo/yr
TOTAL RECOMMENDED $691,537 $447,789 $671,819
6,459,807
kWh
$19,718
-
kW-mo/yr
TOTAL IMPLEMENTED - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs