Assessment Year | 2022 |
---|---|
Principal Product | Door Frames |
NAICS | 332321: Metal Window and Door Manufacturing |
SIC | 3442: Metal Doors, Sash, Frames, Molding, and Trim Manufacturing |
Sales Range | $10 M to 50M |
# of Employees | 100 |
Plant Area |
100,000
ft2
|
Annual Production | 100,000
units
|
Production Hrs. Annual | 4,680
hrs
|
Location (State) | New Jersey |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $18,758 | 382,810 |
kWh
|
$0.049 |
Electricity Demand | $29,753 | 4,647 |
kW-mo/yr
|
$6.40 |
Electricity Fees | $15,679 | - |
|
- |
Natural Gas | $80,397 | 8,730 |
MMBtu
|
$9.21 |
TOTAL YEARLY COSTS | $144,587 | |||
RECOMMENDED SAVINGS* | $19,307 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $335 | $35 |
$252
5,134
kWh
|
$83
-
kW-mo/yr
|
- | |
02 | 2.6125: Keep equipment clean | $1,947 | $1,161 |
$1,947
39,744
kWh
|
- | - | |
03 | 2.2437: Recover waste heat from equipment | $1,971 | $1,200 | - | - |
$1,971
-
MMBtu
|
|
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,261 | $2,600 |
$2,442
49,859
kWh
|
$819
-
kW-mo/yr
|
- | |
05 | 2.7233: Use properly designed and sized hvac equipment | $5,028 | $7,400 | - | - |
$5,028
-
MMBtu
|
|
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,085 | $4,448 |
$1,624
33,140
kWh
|
$461
-
kW-mo/yr
|
- | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,680 | $12,720 |
$4,680
95,497
kWh
|
- | - | |
TOTAL RECOMMENDED | $19,307 | $29,564 |
$10,945
223,374
kWh
|
$1,363
-
kW-mo/yr
|
$6,999
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs