| Assessment Year | 2021 |
|---|---|
| Principal Product | Electronic Connectors |
| NAICS | 334417: Electronic Connector Manufacturing |
| SIC | 3678: Electronic Connectors |
| Sales Range | $10 M to 50M |
| # of Employees | 20 |
| Plant Area |
42,000
ft2
|
| Annual Production | 50,000,000
pieces
|
| Production Hrs. Annual | 8,736
hrs
|
| Location (State) | Pennsylvania |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $113,367 | 1,750,204 |
kWh
|
$0.065 |
| Electricity Demand | $19,924 | 3,894 |
kW-mo/yr
|
$5.12 |
| Electricity Fees | $3,112 | - |
|
- |
| TOTAL YEARLY COSTS | $136,403 | |||
| RECOMMENDED SAVINGS* | $20,872 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $746 | $40 |
$674
10,499
kWh
|
$72
-
kW-mo/yr
|
|
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $6,952 | $14,000 |
$6,266
97,913
kWh
|
$686
-
kW-mo/yr
|
|
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,002 | $32,400 |
$6,230
97,344
kWh
|
$1,772
-
kW-mo/yr
|
|
| 04 | 2.7232: Replace existing hvac unit with high efficiency model | $5,172 | $24,000 |
$4,752
74,256
kWh
|
$420
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $20,872 | $70,440 |
$17,922
280,012
kWh
|
$2,950
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs