Assessment Year | 2019 |
---|---|
Principal Product | Apparel |
NAICS | 315280: Other Cut and Sew Apparel Manufacturing |
SIC | 2389: Apparel and Accessories, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 60 |
Plant Area |
195,000
ft2
|
Annual Production | 1,000,000
units
|
Production Hrs. Annual | 2,600
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $109,037 | 1,651,854 |
kWh
|
$0.066 |
Electricity Demand | $35,797 | 7,669 |
kW-mo/yr
|
$4.67 |
Electricity Fees | $6,713 | - |
|
- |
Natural Gas | $28,728 | 3,310 |
MMBtu
|
$8.68 |
TOTAL YEARLY COSTS | $180,275 | |||
RECOMMENDED SAVINGS* | $47,537 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $20,964 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $418 | $35 |
$296
5,695
kWh
|
$122
-
kW-mo/yr
|
- | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,513 | $4,500 |
$1,135
21,821
kWh
|
$378
-
kW-mo/yr
|
- | |
03 | 2.2523: Reduce infiltration to refrigerated areas; isolate hot equipment from refrigerated areas | $2,440 | $10,500 |
$(-20.0)
(-388)
kWh
|
$(-65.0)
-
kW-mo/yr
|
$2,525
-
MMBtu
|
|
04 | 2.7232: Replace existing hvac unit with high efficiency model | $19,566 | $96,000 |
$15,695
301,821
kWh
|
$3,871
-
kW-mo/yr
|
- | |
05 | 2.7243: Improve air circulation with destratification fans / other methods | $3,054 | $16,000 |
$(-681.0)
(-13,104)
kWh
|
$(-84.0)
-
kW-mo/yr
|
$3,819
-
MMBtu
|
|
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $20,546 | $107,988 |
$15,101
290,411
kWh
|
$5,445
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $47,537 | $235,023 |
$31,526
606,256
kWh
|
$9,667
-
kW-mo/yr
|
$6,344
-
MMBtu
|
||
TOTAL IMPLEMENTED | $20,964 | $108,023 |
$15,397
296,106
kWh
|
$5,567
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs