Assessment Year | 2019 |
---|---|
Principal Product | Hydraulic Turbines |
NAICS | 333511: Industrial Mold Manufacturing |
SIC | 3511: Steam, Gas, and Hydraulic Turbines, and Turbine Generator Set Units |
Sales Range | $1 M to 5M |
# of Employees | 330 |
Plant Area |
400,000
ft2
|
Annual Production | 40
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $370,636 | 7,338,110 |
kWh
|
$0.051 |
Electricity Demand | $70,165 | 20,450 |
kW-mo/yr
|
$3.43 |
Electricity Fees | $52,210 | - |
|
- |
Natural Gas | $173,129 | 26,230 |
MMBtu
|
$6.60 |
TOTAL YEARLY COSTS | $666,140 | |||
RECOMMENDED SAVINGS* | $53,352 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $3,351 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $339 | $310 |
$106
2,150
kWh
|
$233
-
kW-mo/yr
|
- | |
02 | 2.2437: Recover waste heat from equipment | $9,431 | $9,000 | - | - |
$9,431
-
MMBtu
|
|
03 | 2.7312: Minimize use of outside make-up air for ventilation except when used for economizer cycle | $20,437 | $22,500 |
$(-447.0)
(-8,728)
kWh
|
- |
$20,884
-
MMBtu
|
|
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,667 | $6,000 |
$3,372
65,170
kWh
|
$295
-
kW-mo/yr
|
- | |
05 | 2.4323: Use optimum size and capacity equipment | $1,469 | $3,500 |
$1,469
28,799
kWh
|
- | - | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $34 | $105 |
$34
657
kWh
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,351 | $15,513 |
$2,867
56,223
kWh
|
$484
-
kW-mo/yr
|
- | |
08 | 2.7232: Replace existing hvac unit with high efficiency model | $14,624 | $75,000 |
$11,619
227,816
kWh
|
$3,005
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $53,352 | $131,928 |
$19,020
372,087
kWh
|
$4,017
-
kW-mo/yr
|
$30,315
-
MMBtu
|
||
TOTAL IMPLEMENTED | $3,351 | $15,513 |
$2,867
56,223
kWh
|
$484
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs