Assessment Year | 2019 |
---|---|
Principal Product | Paper products |
NAICS | 322230: Stationery Product Manufacturing |
SIC | 2752: Commercial Printing, Lithographic |
Sales Range | $50 M to 100M |
# of Employees | 35 |
Plant Area |
130,000
ft2
|
Annual Production | 13,000
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | New Jersey |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $49,945 | 986,839 |
kWh
|
$0.051 |
Electricity Demand | $33,600 | 4,450 |
kW-mo/yr
|
$7.55 |
Electricity Fees | $18,755 | - |
|
- |
Natural Gas | $28,391 | 3,047 |
MMBtu
|
$9.32 |
TOTAL YEARLY COSTS | $130,691 | |||
RECOMMENDED SAVINGS* | $40,135 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,507 | $1,000 |
$4,285
84,055
kWh
|
$1,222
-
kW-mo/yr
|
- | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $159 | $175 |
$114
2,234
kWh
|
$45
-
kW-mo/yr
|
- | |
03 | 2.2437: Recover waste heat from equipment | $5,321 | $6,000 | - | - |
$5,321
-
MMBtu
|
|
04 | 2.7232: Replace existing hvac unit with high efficiency model | $18,723 | $23,000 |
$17,905
351,086
kWh
|
$818
-
kW-mo/yr
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,425 | $18,125 |
$8,115
159,120
kWh
|
$2,310
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $40,135 | $48,300 |
$30,419
596,495
kWh
|
$4,395
-
kW-mo/yr
|
$5,321
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs