Assessment Year | 2018 |
---|---|
Principal Product | Coils |
NAICS | 334416: Capacitor, Resistor, Coil, Transformer, and Other Inductor Manufacturing |
SIC | 3677: Electronic Coils, Transformers, and Other Inductors |
Sales Range | $5 M to 10M |
# of Employees | 18 |
Plant Area |
38,000
ft2
|
Annual Production | 500,000
units
|
Production Hrs. Annual | 2,340
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $45,009 | 514,085 |
kWh
|
$0.088 |
Electricity Demand | $21,804 | 1,649 |
kW-mo/yr
|
$13.22 |
Electricity Fees | $16,717 | - |
|
- |
Fuel Oil #2 | $20,780 | 995 |
MMBtu
|
$20.88 |
TOTAL YEARLY COSTS | $104,310 | |||
RECOMMENDED SAVINGS* | $22,160 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $22,160 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $214 | $40 |
$214
2,425
kWh
|
- | - | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $114 | $40 |
$48
547
kWh
|
$66
-
kW-mo/yr
|
- | |
03 | 2.1332: Convert combustion equipment to burn natural gas | $10,836 | $28,000 | - | - | $10,836 | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,809 | $23,000 |
$5,478
62,244
kWh
|
$3,331
-
kW-mo/yr
|
- | |
05 | 2.7232: Replace existing hvac unit with high efficiency model | $2,187 | $12,000 |
$1,235
14,040
kWh
|
$952
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $22,160 | $63,080 |
$6,975
79,256
kWh
|
$4,349
-
kW-mo/yr
|
$10,836 | ||
TOTAL IMPLEMENTED | $22,160 | $63,080 |
$6,975
79,256
kWh
|
$4,349
-
kW-mo/yr
|
$10,836 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs