| Assessment Year | 2018 |
|---|---|
| Principal Product | Specialty Chemicals |
| NAICS | 325998: All Other Miscellaneous Chemical Product and Preparation Manufacturing |
| SIC | 2899: Chemicals and Chemical Preparations, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 71 |
| Plant Area |
50,000
ft2
|
| Annual Production | 1,540,000
lb
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Pennsylvania |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $251,012 | 3,857,525 |
kWh
|
$0.065 |
| Electricity Demand | $64,123 | 11,284 |
kW-mo/yr
|
$5.68 |
| Electricity Fees | $11,638 | - |
|
- |
| Natural Gas | $135,316 | 16,700 |
MMBtu
|
$8.10 |
| TOTAL YEARLY COSTS | $462,089 | |||
| RECOMMENDED SAVINGS* | $134,847 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $45,655 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,239 | $70 |
$1,125
17,321
kWh
|
$114
-
kW-mo/yr
|
- | |
| 02 | 2.7232: Replace existing hvac unit with high efficiency model | $53,879 | $30,500 |
$31,686
487,472
kWh
|
$2,948
-
kW-mo/yr
|
$19,245
-
MMBtu
|
|
| 03 | 2.4322: Use or replace with energy efficient substitutes | $6,825 | $7,525 |
$4,780
73,536
kWh
|
$2,045
-
kW-mo/yr
|
- | |
| 04 | 2.6212: Turn off equipment during breaks, reduce operating time | $19,392 | $30,000 |
$17,887
275,184
kWh
|
$1,505
-
kW-mo/yr
|
- | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $22,792 | $85,052 |
$19,924
306,519
kWh
|
$2,868
-
kW-mo/yr
|
- | |
| 06 | 2.1224: Replace boiler | $9,096 | $35,000 | - | - |
$9,096
-
MMBtu
|
|
| 07 | 2.7232: Replace existing hvac unit with high efficiency model | $21,624 | $93,750 |
$19,307
297,024
kWh
|
$2,317
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $134,847 | $281,897 |
$94,709
1,457,056
kWh
|
$11,797
-
kW-mo/yr
|
$28,341
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $45,655 | $178,872 |
$40,356
620,864
kWh
|
$5,299
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs