Assessment Year | 2013 |
---|---|
Principal Product | Metal Tins |
NAICS | 332431: Metal Can Manufacturing |
SIC | 3411: Metal Cans |
Sales Range | $100 M to 500M |
# of Employees | 130 |
Plant Area |
240,000
ft2
|
Annual Production | 360,000,000
pieces
|
Production Hrs. Annual | 5,616
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $244,708 | 5,715,900 |
kWh
|
$0.043 |
Electricity Demand | $34,228 | 16,092 |
kW-mo/yr
|
$2.13 |
Electricity Fees | $133,130 | - |
|
- |
Natural Gas | $344,317 | 52,150 |
MMBtu
|
$6.60 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $137,282 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $134,415 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.7135: Install occupancy sensors | $8,050 | $19,339 |
$7,331
170,493
kWh
|
$411
-
kW-mo/yr
|
$308 | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,100 | $14,365 |
$2,612
60,743
kWh
|
$277
-
kW-mo/yr
|
$211 | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,867 | $8,710 |
$2,342
54,475
kWh
|
$298
-
kW-mo/yr
|
$227 | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,258 | $7,350 |
$1,086
25,247
kWh
|
$26
-
kW-mo/yr
|
$1,146 | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $50,065 | $1,470 |
$41,903
974,486
kWh
|
$8,162
-
kW-mo/yr
|
- | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $50,836 | $87,600 |
$47,098
1,095,304
kWh
|
$3,738
-
kW-mo/yr
|
- | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,083 | $1,000 |
$1,930
44,894
kWh
|
$153
-
kW-mo/yr
|
- | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $18,023 | $32,025 |
$16,696
388,268
kWh
|
$1,327
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $137,282 | $171,859 |
$120,998
2,813,910
kWh
|
$14,392
-
kW-mo/yr
|
$1,892 | ||
TOTAL IMPLEMENTED | $134,415 | $163,149 |
$118,656
2,759,435
kWh
|
$14,094
-
kW-mo/yr
|
$1,665 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs