Assessment Year | 2013 |
---|---|
Principal Product | fasteners |
NAICS | 332722: Bolt, Nut, Screw, Rivet, and Washer Manufacturing |
SIC | 3452: Bolts, Nuts, Screws, Rivets, and Washers |
Sales Range | $50 M to 100M |
# of Employees | 99 |
Plant Area |
270,000
ft2
|
Annual Production | 100,000
lb
|
Production Hrs. Annual | 2,574
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $375,455 | 8,728,816 |
kWh
|
$0.043 |
Electricity Demand | $67,848 | 18,980 |
kW-mo/yr
|
$3.57 |
Electricity Fees | $271,602 | - |
|
- |
Natural Gas | $238,756 | 37,414 |
MMBtu
|
$6.38 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $150,990 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $67,416 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $59,031 | $85,300 |
$44,272
1,029,600
kWh
|
$6,426
-
kW-mo/yr
|
- | $8,333 | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,371 | $13,013 |
$1,992
46,330
kWh
|
$496
-
kW-mo/yr
|
- | $883 | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,725 | $20,280 |
$11,589
269,508
kWh
|
$1,482
-
kW-mo/yr
|
- | $654 | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,978 | $1,000 |
$4,347
101,089
kWh
|
$631
-
kW-mo/yr
|
- | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,529 | $2,139 |
$212
4,922
kWh
|
$1,317
-
kW-mo/yr
|
- | - | |
06 | 2.7232: Replace existing hvac unit with high efficiency model | $6,405 | $21,000 |
$5,283
122,850
kWh
|
$50
-
kW-mo/yr
|
$1,072
-
MMBtu
|
- | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,878 | $3,800 |
$1,139
26,482
kWh
|
$739
-
kW-mo/yr
|
- | - | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $7,215 | $24,200 |
$6,476
150,616
kWh
|
$739
-
kW-mo/yr
|
- | - | |
09 | 2.2443: Re-use or recycle hot or cold process exhaust air | $13,848 | $6,600 | - | - |
$13,848
-
MMBtu
|
- | |
10 | 2.2443: Re-use or recycle hot or cold process exhaust air | $4,751 | $5,000 | - | - |
$4,751
-
MMBtu
|
- | |
11 | 2.2443: Re-use or recycle hot or cold process exhaust air | $4,613 | $14,000 | - | - |
$4,613
-
MMBtu
|
- | |
12 | 2.7312: Minimize use of outside make-up air for ventilation except when used for economizer cycle | $29,646 | $29,648 |
$17,632
410,041
kWh
|
- |
$12,014
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $150,990 | $225,980 |
$92,942
2,161,438
kWh
|
$11,880
-
kW-mo/yr
|
$36,298
-
MMBtu
|
$9,870 | ||
TOTAL IMPLEMENTED | $67,416 | $92,239 |
$49,970
1,162,093
kWh
|
$9,113
-
kW-mo/yr
|
- | $8,333 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs