Assessment Year | 2012 |
---|---|
Principal Product | Flavors and Fragrances |
NAICS | 325611: Soap and Other Detergent Manufacturing |
SIC | 2844: Perfumes, Cosmetics, and Other Toilet Preparations |
Sales Range | $100 M to 500M |
# of Employees | 29 |
Plant Area |
36,000
ft2
|
Annual Production | 7,000,000,000
ton
|
Production Hrs. Annual | 2,080
hrs
|
Location (State) | New Jersey |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $104,432 | 1,069,566 |
kWh
|
$0.098 |
Electricity Demand | $27,794 | 3,885 |
kW-mo/yr
|
$7.15 |
Natural Gas | $67,468 | 16,507 |
MMBtu
|
$4.09 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $33,224 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,307 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,060 | $40 |
$745
7,601
kWh
|
$315
-
kW-mo/yr
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,654 | $1,000 |
$2,567
26,196
kWh
|
$1,087
-
kW-mo/yr
|
- | - | |
03 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $6,115 | - |
$6,115
62,400
kWh
|
- | - | - | |
04 | 2.1233: Analyze flue gas for proper air/fuel ratio | $653 | $2,000 | - | - |
$653
-
MMBtu
|
- | |
05 | 2.2442: Preheat combustion air with waste heat | $5,309 | $20,000 | - | - |
$5,309
-
MMBtu
|
- | |
06 | 2.7496: Install partitions to reduce size of conditioned space | $10,156 | $16,300 | - | - |
$156
-
MMBtu
|
$10,000 | |
07 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $4,814 | $9,000 |
$4,485
45,760
kWh
|
$1,129
-
kW-mo/yr
|
$(-800.0)
-
MMBtu
|
- | |
08 | 2.2135: Repair and eliminate steam leaks | $475 | $675 | - | - |
$475
-
MMBtu
|
- | |
09 | 2.7232: Replace existing hvac unit with high efficiency model | $988 | $4,050 |
$688
7,020
kWh
|
$300
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $33,224 | $53,065 |
$14,600
148,977
kWh
|
$2,831
-
kW-mo/yr
|
$5,793
-
MMBtu
|
$10,000 | ||
TOTAL IMPLEMENTED | $21,307 | $40,015 |
$3,312
33,797
kWh
|
$1,401
-
kW-mo/yr
|
$6,593
-
MMBtu
|
$10,000 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs