| Assessment Year | 2011 |
|---|---|
| Principal Product | Switches and Connectors |
| NAICS | 334419: Other Electronic Component Manufacturing |
| SIC | 3679: Electronic Components, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 34 |
| Plant Area |
56,000
ft2
|
| Annual Production | 0
units
|
| Production Hrs. Annual | 6,120
hrs
|
| Location (State) | Pennsylvania |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $239,733 | 3,132,577 |
kWh
|
$0.077 |
| Electricity Demand | $114,952 | 8,969 |
kW-mo/yr
|
$12.82 |
| Natural Gas | $54,729 | 4,922 |
MMBtu
|
$11.12 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $73,594 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $43,690 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $21,447 | $60,000 |
$16,166
209,946
kWh
|
$5,281
-
kW-mo/yr
|
- | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,435 | $12,420 |
$9,365
121,617
kWh
|
$3,501
-
kW-mo/yr
|
- | $569 | |
| 03 | 2.7232: Replace existing hvac unit with high efficiency model | $12,853 | $18,000 |
$942
12,240
kWh
|
$51
-
kW-mo/yr
|
$11,860
-
MMBtu
|
- | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,650 | $3,000 |
$5,009
65,055
kWh
|
$1,641
-
kW-mo/yr
|
- | - | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,369 | $15,675 |
$4,169
54,142
kWh
|
$2,038
-
kW-mo/yr
|
- | $162 | |
| 06 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $5,743 | $3,000 | - |
$5,743
-
kW-mo/yr
|
- | - | |
| 07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,383 | $2,500 |
$216
2,800
kWh
|
$4,167
-
kW-mo/yr
|
- | - | |
| 08 | 2.7135: Install occupancy sensors | $2,714 | $540 |
$2,714
32,251
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $73,594 | $115,135 |
$38,581
498,051
kWh
|
$22,422
-
kW-mo/yr
|
$11,860
-
MMBtu
|
$731 | ||
| TOTAL IMPLEMENTED | $43,690 | $51,595 |
$19,701
255,854
kWh
|
$11,398
-
kW-mo/yr
|
$11,860
-
MMBtu
|
$731 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs