Assessment Year | 2011 |
---|---|
Principal Product | Wood doors |
NAICS | 321911: Wood Window and Door Manufacturing |
SIC | 2431: Millwork |
Sales Range | $10 M to 50M |
# of Employees | 215 |
Plant Area |
187,800
ft2
|
Annual Production | 420,000
units
|
Production Hrs. Annual | 4,000
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $414,816 | 4,522,200 |
kWh
|
$0.092 |
Electricity Demand | $90,086 | 16,358 |
kW-mo/yr
|
$5.51 |
Natural Gas | $107,899 | 10,200 |
MMBtu
|
$10.58 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $77,772 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $18,773 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $25,497 | $12,000 |
$21,986
238,975
kWh
|
$3,511
-
kW-mo/yr
|
- | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $11,409 | $580 |
$9,838
106,930
kWh
|
$1,571
-
kW-mo/yr
|
- | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $10,295 | $15,000 | - | - |
$10,295
-
MMBtu
|
|
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,832 | $1,420 |
$5,028
54,657
kWh
|
$804
-
kW-mo/yr
|
- | |
05 | 2.2511: Insulate bare equipment | $4,063 | $8,007 | - | - |
$4,063
-
MMBtu
|
|
06 | 2.6121: Reduce hot water temperature to the minimum required | $1,532 | - | - | - |
$1,532
-
MMBtu
|
|
07 | 2.7232: Replace existing hvac unit with high efficiency model | $3,127 | $7,000 |
$1,794
19,500
kWh
|
- |
$1,333
-
MMBtu
|
|
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $16,017 | $39,066 |
$14,072
152,963
kWh
|
$1,945
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $77,772 | $83,073 |
$52,718
573,025
kWh
|
$7,831
-
kW-mo/yr
|
$17,223
-
MMBtu
|
||
TOTAL IMPLEMENTED | $18,773 | $2,000 |
$14,866
161,587
kWh
|
$2,375
-
kW-mo/yr
|
$1,532
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs