| Assessment Year | 2004 |
|---|---|
| Principal Product | Windshield Water Nozzles |
| NAICS | 336320: Motor Vehicle Electrical and Electronic Equipment Manufacturing |
| SIC | 3714: Motor Vehicle Parts and Accessories |
| Sales Range | $10 M to 50M |
| # of Employees | 350 |
| Plant Area |
89,000
ft2
|
| Annual Production | 48,000,000
pieces
|
| Production Hrs. Annual | 6,000
hrs
|
| Location (State) | Maryland |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $177,771 | 3,906,890 |
kWh
|
$0.046 |
| Electricity Demand | $93,679 | 8,926 |
kW-mo/yr
|
$10.50 |
| Natural Gas | $10,648 | 1,242 |
MMBtu
|
$8.57 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $44,589 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $19,266 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $15,732 | $1,000 |
$2,429
52,793
kWh
|
$13,303
-
kW-mo/yr
|
- | |
| 02 | 2.3212: Optimize plant power factor | $9,843 | $17,200 | - | - | $9,843 | |
| 03 | 2.4226: Use / purchase optimum sized compressor | $6,132 | $8,028 |
$4,662
101,348
kWh
|
$1,470
-
kW-mo/yr
|
- | |
| 04 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $4,694 | $2,500 | - |
$4,694
-
kW-mo/yr
|
- | |
| 05 | 2.4238: Do not use compressed air for personal cooling | $3,459 | $1,200 |
$2,378
51,692
kWh
|
$1,081
-
kW-mo/yr
|
- | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,947 | $11,665 |
$1,543
33,543
kWh
|
$1,404
-
kW-mo/yr
|
- | |
| 07 | 2.7135: Install occupancy sensors | $1,782 | $3,900 |
$1,782
38,743
kWh
|
- | - | |
| TOTAL RECOMMENDED | $44,589 | $45,493 |
$12,794
278,119
kWh
|
$21,952
-
kW-mo/yr
|
$9,843 | ||
| TOTAL IMPLEMENTED | $19,266 | $35,265 |
$3,325
72,286
kWh
|
$6,098
-
kW-mo/yr
|
$9,843 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs