| Assessment Year | 2002 |
|---|---|
| Principal Product | Corrugated Paper packaging |
| NAICS |
n/a
|
| SIC | 2653: Corrugated and Solid Fiber Boxes |
| Sales Range | $10 M to 50M |
| # of Employees | 95 |
| Plant Area |
240,000
ft2
|
| Annual Production | 480,000,000
pieces
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Pennsylvania |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $152,289 | 1,982,000 |
kWh
|
$0.077 |
| Electricity Demand | $36,738 | 5,371 |
kW-mo/yr
|
$6.84 |
| Natural Gas | $150,021 | 14,447 |
MMBtu
|
$10.38 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $51,468 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $38,742 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.3212: Optimize plant power factor | $10,572 | $15,000 | - | - | $10,572 | - | |
| 02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $23,457 | $1,500 | - | - | - |
$23,457
-
MMBtu
|
|
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,609 | $25,249 |
$11,566
167,623
kWh
|
$1,043
-
kW-mo/yr
|
- | - | |
| 04 | 2.7135: Install occupancy sensors | $433 | $900 |
$433
5,777
kWh
|
- | - | - | |
| 05 | 2.2611: Moderate cooling tower outlet temperature | $1,721 | $245 | - | - | - |
$1,721
-
MMBtu
|
|
| 06 | 2.4221: Install compressor air intakes in coolest locations | $2,676 | $1,200 |
$2,234
29,094
kWh
|
$442
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $51,468 | $44,094 |
$14,233
202,494
kWh
|
$1,485
-
kW-mo/yr
|
$10,572 |
$25,178
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $38,742 | $27,949 |
$13,800
196,717
kWh
|
$1,485
-
kW-mo/yr
|
- |
$23,457
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs