Assessment Year | 1997 |
---|---|
Principal Product | kitchen and bath cabinetry |
NAICS |
n/a
|
SIC | 2434: Wood Kitchen Cabinets |
Sales Range | $5 M to 10M |
# of Employees | 125 |
Plant Area |
36,000
ft2
|
Annual Production | 1,400
units
|
Production Hrs. Annual | 2,600
hrs
|
Location (State) | Kansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $44,236 | 693,728 |
kWh
|
$0.064 |
Electricity Demand | $13,098 | 3,180 |
kW-mo/yr
|
$4.12 |
Natural Gas | $9,655 | 1,952 |
MMBtu
|
$4.95 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $122,180 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $40,590 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Primary Raw Material Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.2492: Use "heat wheel" or other heat exchanger to cross-exchange building exhaust air with make-up air | $4,260 | $30,000 | - | - |
$4,260
-
MMBtu
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,250 | $310 |
$1,720
27,843
kWh
|
$530
-
kW-mo/yr
|
- | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,290 | $5,500 |
$990
15,826
kWh
|
$300
-
kW-mo/yr
|
- | - | - | |
04 | 2.4133: Use most efficient type of electric motors | $990 | $4,090 |
$710
11,430
kWh
|
$280
-
kW-mo/yr
|
- | - | - | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $820 | $230 |
$590
9,379
kWh
|
$230
-
kW-mo/yr
|
- | - | - | |
06 | 2.7135: Install occupancy sensors | $490 | $250 |
$490
7,913
kWh
|
- | - | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $360 | $480 |
$160
2,638
kWh
|
$20
-
kW-mo/yr
|
- | $180 | - | |
08 | 3.2123: Convert to high volume low pressure (hvlp) paint guns | $74,200 | $1,500 | - | - | - | - | $74,200 | |
09 | 4.711: Initiate a total quality management program | $37,520 | $11,790 | - | - | - | $37,520 | - | |
TOTAL RECOMMENDED | $122,180 | $54,150 |
$4,660
75,029
kWh
|
$1,360
-
kW-mo/yr
|
$4,260
-
MMBtu
|
$37,700 | $74,200 | ||
TOTAL IMPLEMENTED | $40,590 | $12,330 |
$2,310
37,222
kWh
|
$760
-
kW-mo/yr
|
- | $37,520 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Primary Raw Material Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs