| Assessment Year | 1994 |
|---|---|
| Principal Product | Cellular telephones |
| NAICS |
n/a
|
| SIC | 3663: Radio and Television Broadcasting and Communications Equipment |
| Sales Range | $10 M to 50M |
| # of Employees | 150 |
| Plant Area |
47,700
ft2
|
| Annual Production | 600,000
pieces
|
| Production Hrs. Annual | 4,160
hrs
|
| Location (State) | Nebraska |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $82,245 | 1,871,923 |
kWh
|
$0.044 |
| Natural Gas | $9,357 | 2,210 |
MMBtu
|
$4.23 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $11,283 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,417 | $35,256 |
$7,417
132,474
kWh
|
|
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,023 | $1,325 |
$1,023
13,775
kWh
|
|
| 03 | 2.7135: Install occupancy sensors | $914 | $990 |
$914
20,809
kWh
|
|
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $191 | $300 |
$191
1,758
kWh
|
|
| 05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $824 | $150 |
$824
18,757
kWh
|
|
| 06 | 2.4221: Install compressor air intakes in coolest locations | $283 | $116 |
$283
6,448
kWh
|
|
| 07 | 2.2511: Insulate bare equipment | $631 | $497 |
$631
14,361
kWh
|
|
| TOTAL RECOMMENDED | $11,283 | $38,634 |
$11,283
208,382
kWh
|
||
| TOTAL IMPLEMENTED | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs