Assessment Year | 1990 |
---|---|
Principal Product | PLASTIC AUTO. LENSES |
NAICS |
n/a
|
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 160 |
Plant Area |
n/a
|
Annual Production | 4,800,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $311,286 | 4,594,080 |
kWh
|
$0.068 |
Natural Gas | $4,994 | 1,190 |
MMBtu
|
$4.20 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $29,385 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $16,233 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,155 | $4,288 |
$4,155
61,254
kWh
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,513 | $280 |
$3,513
51,876
kWh
|
- | |
03 | 2.2621: Modify refrigeration system to operate at a lower pressure | $12,188 | $18,000 |
$12,188
179,953
kWh
|
- | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $734 | - |
$734
10,844
kWh
|
- | |
05 | 2.3191: Use demand controller or load shedder | $8,069 | $1,000 |
$8,069
-
kWh
|
- | |
06 | 2.6121: Reduce hot water temperature to the minimum required | $496 | - |
$496
7,327
kWh
|
- | |
07 | 2.8112: Combine utility meters | $230 | $150 | - |
$230
-
MMBtu
|
|
TOTAL RECOMMENDED | $29,385 | $23,718 |
$29,155
311,254
kWh
|
$230
-
MMBtu
|
||
TOTAL IMPLEMENTED | $16,233 | $5,568 |
$16,233
120,457
kWh
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs