| Assessment Year | 2025 |
|---|---|
| Principal Product | Flexible Hose |
| NAICS | 326220: Rubber and Plastics Hoses and Belting Manufacturing |
| SIC | 3052: Rubber and Plastics Hose and Belting |
| Sales Range | $100 M to 500M |
| # of Employees | 180 |
| Plant Area |
440,000
ft2
|
| Annual Production | 250,000
thousand feet
|
| Production Hrs. Annual | 6,000
hrs
|
| Location (State) | South Carolina |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $467,844 | 6,915,480 |
kWh
|
$0.068 | |
| Electricity Demand | $74,997 | 15,119 |
kW-mo/yr
|
$4.96 | |
| Natural Gas | $17,171 | 15,660 |
MMBtu
|
$1.10 | |
| Waste Disposal Costs | |||||
| Water Usage | $10,640 | 1,085 |
Tgal
|
$9.81 | |
| Water Disposal | $13,043 | 1,085 |
Tgal
|
$12.02 | |
| TOTAL YEARLY COSTS | $583,695 | ||||
| RECOMMENDED SAVINGS* | $127,857 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $25,030 | $29,920 |
$22,756
334,653
kWh
|
$2,274
-
kW-mo/yr
|
- | |
| 02 | 2.7232: Replace existing hvac unit with high efficiency model | $49,140 | $229,656 |
$44,676
657,000
kWh
|
$4,464
-
kW-mo/yr
|
- | |
| 03 | 2.8112: Combine utility meters | $5,464 | $22,500 | - | - | $5,464 | |
| 04 | 2.9114: Use solar heat to make electricty | $48,223 | $476,700 |
$42,143
619,762
kWh
|
$6,080
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $127,857 | $758,776 |
$109,575
1,611,415
kWh
|
$12,818
-
kW-mo/yr
|
$5,464 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs