Assessment Year 2023
Principal Product Fabricated Metal Products
NAICS 332999: All Other Miscellaneous Fabricated Metal Product Manufacturing
SIC 3499: Fabricated Metal Products, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 180
Plant Area 160,000
ft2
Annual Production 1,200,000
units
Production Hrs. Annual 7,140
hrs
Location (State) South Carolina

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $127,137 2,686,516
kWh
Electricity Demand $111,656 7,978
kW-mo/yr
Natural Gas $7,969 811
MMBtu
Waste Disposal Costs
Water Usage $6,682 1,239
Tgal
Water Disposal $11,590 1,239
Tgal
TOTAL YEARLY COSTS $265,034
RECOMMENDED SAVINGS* $137,268 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Administrative Changes Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $6,385 $5,960 $4,264
90,155
kWh
$2,121
-
kW-mo/yr
- -
02 2.4231: Reduce the pressure of compressed air to the minimum required $593 $60 $396
8,369
kWh
$197
-
kW-mo/yr
- -
03 2.2449: Recover heat from exhausted steam, hot air or hot water $2,009 $5,440 - - $2,009
-
MMBtu
-
04 2.4111: Utilize energy-efficient belts and other improved mechanisms $307 $119 $112
2,366
kWh
$195
-
kW-mo/yr
- -
05 2.7142: Utilize higher efficiency lamps and/or ballasts $4,663 $19,796 $1,891
39,984
kWh
$941
-
kW-mo/yr
- $1,831
06 2.9114: Use solar heat to make electricty $123,311 $1,196,880 $109,507
1,871,456
kWh
$13,804
-
kW-mo/yr
- -
TOTAL RECOMMENDED $137,268 $1,228,255 $116,170
2,012,330
kWh
$17,258
-
kW-mo/yr
$2,009
-
MMBtu
$1,831
TOTAL IMPLEMENTED - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs