| Assessment Year | 2023 | 
|---|---|
| Principal Product | Plastic Caps | 
| NAICS | 326199: All Other Plastics Product Manufacturing | 
| SIC | 3089: Plastics Products, Not Elsewhere Classified | 
| Sales Range | $50 M  to 100M  | 
    
| # of Employees | 57 | 
| Plant Area | 
                            220,000
                 
ft2
 
                     | 
    
| Annual Production | 3,400,000,000
             
pieces
 
         | 
    
| Production Hrs. Annual | 8,400
             
hrs
 
         | 
    
| Location (State) | Georgia | 
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $1,492,017 | 28,070,809 | 
             
kWh
 
         | 
        $0.053 | |
| Natural Gas | $3,709 | 309 | 
             
MMBtu
 
         | 
        $12.01 | |
| Waste Disposal Costs | |||||
| Water Usage | $4,065 | 560 | 
             
Tgal
 
         | 
        $7.26 | |
| Water Disposal | $4,558 | 560 | 
             
Tgal
 
         | 
        $8.14 | |
| TOTAL YEARLY COSTS | $1,504,349 | ||||
| RECOMMENDED SAVINGS* | $77,423 | 
             See individual recommendations below 
            *Non-energy impacts included in savings.
         | 
    |||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Administrative Changes Savings | 
|---|---|---|---|---|---|---|
| 01 | 2.4235: Remove or close off unneeded compressed air lines | $14,419 | $320 | 
                        $14,419
                                                     271,035
                                 
                                            
kWh
 
                             | 
                                                                                - | |
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,203 | $60 | 
                        $3,203
                                                     60,209
                                 
                                            
kWh
 
                             | 
                                                                                - | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,814 | $28,960 | 
                        $10,814
                                                     203,280
                                 
                                            
kWh
 
                             | 
                                                                                - | |
| 04 | 2.6127: Maintain air filters by cleaning or replacement | $2,238 | $1,864 | 
                        $2,238
                                                     42,069
                                 
                                            
kWh
 
                             | 
                                                                                - | |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $224 | $765 | 
                        $224
                                                     4,207
                                 
                                            
kWh
 
                             | 
                                                                                - | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,448 | $8,951 | 
                        $1,226
                                                     23,050
                                 
                                            
kWh
 
                             | 
                                                                                $2,222 | |
| 07 | 2.9114: Use solar heat to make electricty | $43,077 | $421,486 | 
                        $43,077
                                                     667,626
                                 
                                            
kWh
 
                             | 
                                                                                - | |
| TOTAL RECOMMENDED | $77,423 | $462,406 | 
                        $75,201
                                                     1,271,476
                                 
                                            
kWh
 
                             | 
                                                                                $2,222 | ||
| TOTAL IMPLEMENTED | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs