ITAC Assessment: KS2312
ITAC logo
ITAC Assessment: KS2312
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2023
Principal Product Electrical and Wiring Parts
NAICS 335931: Current-Carrying Wiring Device Manufacturing
SIC 3643: Current-Carrying Wiring Devices
Sales Range $10
M
to 50
M
# of Employees 43
Plant Area 24,000
ft2
Annual Production 5,400,000
pieces
Production Hrs. Annual 2,080
hrs
Location (State) Georgia

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $90,773 684,960
kWh
Natural Gas $11,433 928
MMBtu
Waste Disposal Costs
Water Usage $939 119
Tgal
Water Disposal $2,560 119
Tgal
TOTAL YEARLY COSTS $105,705
RECOMMENDED SAVINGS* $91,377 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $34,794

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Fees Savings Administrative Changes Savings One-time Revenue or Avoided Cost Savings
01 2.8121: Apply for tax-free status for energy purchases $20,360 $1,600 - $5,090 - $15,270
02 2.2522: Isolate hot or cold equipment $3,369 $3,164 $3,369
25,428
kWh
- - -
03 2.6212: Turn off equipment during breaks, reduce operating time $2,204 - $2,984
22,519
kWh
- $(-780.0) -
04 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $3,944 $5,480 $3,944
29,763
kWh
- - -
05 2.4111: Utilize energy-efficient belts and other improved mechanisms $80 $89 $80
607
kWh
- - -
06 2.7232: Replace existing hvac unit with high efficiency model $8,286 $62,649 $8,286
62,539
kWh
- - -
07 2.9114: Use solar heat to make electricty $53,134 $373,105 $53,134
401,009
kWh
- - -
TOTAL RECOMMENDED $91,377 $446,087 $71,797
541,865
kWh
$5,090 $(-780.0) $15,270
TOTAL IMPLEMENTED $34,794 $69,729 $15,214
114,821
kWh
$5,090 $(-780.0) $15,270
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Fees Savings Administrative Changes Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs