Assessment Year | 1996 |
---|---|
Principal Product | Motor Castings, Historical Markers and custom made parts. |
NAICS |
n/a
|
SIC | 3321: Gray and Ductile Iron Foundries |
Sales Range | $5 M to 10M |
# of Employees | 100 |
Plant Area |
70,000
ft2
|
Annual Production | 3,000
ton
|
Production Hrs. Annual | 2,613
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $124,645 | 3,909,144 |
kWh
|
$0.032 |
Electricity Demand | $110,348 | 17,725 |
kW-mo/yr
|
$6.23 |
Electricity Fees | $1,560 | - |
|
- |
Natural Gas | $30,421 | 9,224 |
MMBtu
|
$3.30 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $11,232 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $6,498 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings |
---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $5,652 | $12,200 |
$3,849
120,750
kWh
|
$1,803
-
kW-mo/yr
|
- | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,970 | $3,560 |
$1,544
48,359
kWh
|
$1,426
-
kW-mo/yr
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $846 | $343 |
$438
13,775
kWh
|
$408
-
kW-mo/yr
|
- | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $481 | $20 |
$481
14,947
kWh
|
- | - | |
05 | 3.4112: Recovery metals from rinse water(evap., ion exchange, ro, electrolysis, electrodialysis) and reuse rinse water | $1,283 | $651 | - | - |
$1,283
-
Tgal
|
|
TOTAL RECOMMENDED | $11,232 | $16,774 |
$6,312
197,831
kWh
|
$3,637
-
kW-mo/yr
|
$1,283
-
Tgal
|
||
TOTAL IMPLEMENTED | $6,498 | $12,543 |
$4,287
134,525
kWh
|
$2,211
-
kW-mo/yr
|
- |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs