| Assessment Year | 1995 |
|---|---|
| Principal Product | Custom Injection Molded Thermoplastic Parts |
| NAICS |
n/a
|
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $100 M to 500M |
| # of Employees | 65 |
| Plant Area |
97,000
ft2
|
| Annual Production | 2,600,000
lb
|
| Production Hrs. Annual | 8,592
hrs
|
| Location (State) | Texas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $238,540 | 4,293,669 |
kWh
|
$0.056 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $83,469 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $58,837 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.3511: Use plant owned transformers or lease transformers | $28,787 | $7,200 |
$28,787
541,325
kWh
|
|
| 02 | 2.3134: Shift from daytime to nighttime operation | $21,682 | - |
$21,682
347,304
kWh
|
|
| 03 | 2.2511: Insulate bare equipment | $20,807 | $284 |
$20,807
390,973
kWh
|
|
| 04 | 2.4133: Use most efficient type of electric motors | $7,160 | $6,450 |
$7,160
141,559
kWh
|
|
| 05 | 2.2628: Utilize a less expensive cooling method | $2,950 | $60 |
$2,950
88,218
kWh
|
|
| 06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,632 | $20 |
$1,632
30,774
kWh
|
|
| 07 | 2.7135: Install occupancy sensors | $451 | $325 |
$451
13,482
kWh
|
|
| TOTAL RECOMMENDED | $83,469 | $14,339 |
$83,469
1,553,635
kWh
|
||
| TOTAL IMPLEMENTED | $58,837 | $14,279 |
$58,837
1,118,113
kWh
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs