| Assessment Year | 2026 |
|---|---|
| Principal Product | HVAC Centrifugal Fans |
| NAICS | 333415: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipmen |
| SIC | 3564: Industrial and Commercial Fans and Blowers and Air Purification Equipment |
| Sales Range | $50 M to 100M |
| # of Employees | 230 |
| Plant Area |
126,550
ft2
|
| Annual Production | 364,566
pieces
|
| Production Hrs. Annual | 4,680
hrs
|
| Location (State) | Indiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $184,370 | 1,824,340 |
kWh
|
$0.10 |
| Natural Gas | $87,917 | 11,579 |
MMBtu
|
$7.59 |
| LPG | $62,380 | 19,494 |
MMBtu
|
$3.20 |
| TOTAL YEARLY COSTS | $334,667 | |||
| RECOMMENDED SAVINGS* | $210,530 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | LPG Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $6,083 | - |
$6,083
60,228
kWh
|
- | - | |
| 02 | 2.7314: Reduce ventilation air | $35,653 | $3,000 |
$32,317
319,969
kWh
|
$3,336
-
MMBtu
|
- | |
| 03 | 2.7224: Reduce space conditioning during non-working hours | $4,468 | $310 |
$1,212
12,000
kWh
|
$3,256
-
MMBtu
|
- | |
| 04 | 2.7135: Install occupancy sensors | $8,132 | $700 |
$8,132
80,511
kWh
|
- | - | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,187 | $440 |
$4,187
41,456
kWh
|
- | - | |
| 06 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $22,821 | $5,550 |
$22,821
225,948
kWh
|
- | - | |
| 07 | 2.6218: Turn off equipment when not in use | $10,343 | $3,625 |
$10,343
102,411
kWh
|
- | - | |
| 08 | 2.6218: Turn off equipment when not in use | $4,427 | $2,340 |
$4,427
43,830
kWh
|
- | - | |
| 09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $64,217 | $51,340 |
$64,217
635,808
kWh
|
- | - | |
| 10 | 2.1321: Replace fossil fuel equipment with electrical equipment | $48,200 | $100,000 |
$(-14,180.0)
(-140,400)
kWh
|
- |
$62,380
-
MMBtu
|
|
| 11 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,999 | $4,180 |
$1,999
19,793
kWh
|
- | - | |
| TOTAL RECOMMENDED | $210,530 | $171,485 |
$141,558
1,401,554
kWh
|
$6,592
-
MMBtu
|
$62,380
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | LPG Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs