| Assessment Year | 2025 |
|---|---|
| Principal Product | Medical Device |
| NAICS | 327215: Glass Product Manufacturing Made of Purchased Glass |
| SIC | 3221: Glass Containers |
| Sales Range | $10 M to 50M |
| # of Employees | 230 |
| Plant Area |
560,000
ft2
|
| Annual Production | 1,740,000
pieces
|
| Production Hrs. Annual | 8,400
hrs
|
| Location (State) | Indiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $597,337 | 11,870,244 |
kWh
|
$0.050 | |
| Electricity Demand | $602,322 | 24,713 |
kW-mo/yr
|
$24.37 | |
| Electricity Fees | $32,839 | - |
|
- | |
| Natural Gas | $42,737 | 5,836 |
MMBtu
|
$7.32 | |
| Other Gas | $2,461 | 1 |
MMBtu
|
$2,461.26 | |
| Waste Disposal Costs | |||||
| Water Usage | $108,849 | 24,510 |
Tgal
|
$4.44 | |
| TOTAL YEARLY COSTS | $1,386,545 | ||||
| RECOMMENDED SAVINGS* | $124,294 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7226: Use computer programs to optimize hvac performance | $49,158 | - |
$28,980
579,600
kWh
|
$20,178
-
kW-mo/yr
|
|
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $46,665 | - |
$27,510
550,190
kWh
|
$19,155
-
kW-mo/yr
|
|
| 03 | 2.7224: Reduce space conditioning during non-working hours | $18,398 | - |
$9,040
180,800
kWh
|
$9,358
-
kW-mo/yr
|
|
| 04 | 2.7135: Install occupancy sensors | $10,073 | $3,780 |
$10,073
201,466
kWh
|
- | |
| TOTAL RECOMMENDED | $124,294 | $3,780 |
$75,603
1,512,056
kWh
|
$48,691
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs