Assessment Year | 2025 |
---|---|
Principal Product | Plastic Products |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 45 |
Plant Area |
42,080
ft2
|
Annual Production | 39,900,000
units
|
Production Hrs. Annual | 6,360
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $197,068 | 2,120,224 |
kWh
|
$0.093 | |
Electricity Demand | $36,793 | 5,533 |
kW-mo/yr
|
$6.65 | |
Electricity Fees | $23,245 | - |
|
- | |
Natural Gas | $2,851 | 234 |
MMBtu
|
$12.18 | |
Waste Disposal Costs | |||||
Water Usage | $2,793 | 137 |
Tgal
|
$20.39 | |
Water Disposal | $1,446 | 137 |
Tgal
|
$10.55 | |
TOTAL YEARLY COSTS | $264,196 | ||||
RECOMMENDED SAVINGS* | $51,872 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.6212: Turn off equipment during breaks, reduce operating time | $3,572 | - |
$3,572
22,050
kWh
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,420 | $50 |
$1,878
21,096
kWh
|
$542
-
kW-mo/yr
|
- | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $524 | - |
$431
5,429
kWh
|
$93
-
kW-mo/yr
|
- | |
04 | 2.2691: Shut off cooling if cold outside air will cool process | $1,666 | $82 |
$1,666
10,281
kWh
|
- | - | |
05 | 2.7212: Install or upgrade insulation on hvac distribution systems | $1,484 | $373 |
$1,484
9,158
kWh
|
- | - | |
06 | 2.7135: Install occupancy sensors | $705 | $200 |
$705
7,925
kWh
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $17,254 | $8,190 |
$15,243
94,090
kWh
|
$2,011
-
kW-mo/yr
|
- | |
08 | 2.3212: Optimize plant power factor | $23,307 | $34,470 | - | - | $23,307 | |
09 | 2.4221: Install compressor air intakes in coolest locations | $940 | $1,742 |
$743
8,352
kWh
|
$197
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $51,872 | $45,107 |
$25,722
178,381
kWh
|
$2,843
-
kW-mo/yr
|
$23,307 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs