| Assessment Year | 2024 |
|---|---|
| Principal Product | Temperature Sensors |
| NAICS | 334519: Other Measuring and Controlling Device Manufacturing |
| SIC | 3823: Industrial Instruments for Measurement, Display, and Control of Process Variables; and Related Products |
| Sales Range | $10 M to 50M |
| # of Employees | 205 |
| Plant Area |
86,777
ft2
|
| Annual Production | 500,000
pieces
|
| Production Hrs. Annual | 4,872
hrs
|
| Location (State) | Indiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $231,486 | 2,377,081 |
kWh
|
$0.097 | |
| Electricity Demand | $48,460 | 6,655 |
kW-mo/yr
|
$7.28 | |
| Electricity Fees | $3,400 | - |
|
- | |
| Natural Gas | $31,528 | 3,111 |
MMBtu
|
$10.13 | |
| Waste Disposal Costs | |||||
| Water Usage | $7,143 | 445 |
Tgal
|
$16.04 | |
| Water Disposal | $12,574 | 445 |
Tgal
|
$28.23 | |
| TOTAL YEARLY COSTS | $334,591 | ||||
| RECOMMENDED SAVINGS* | $51,014 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $23,144 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,623 | - |
$3,608
37,975
kWh
|
$1,015
-
kW-mo/yr
|
- | |
| 02 | 2.2211: Use optimum temperature | $2,876 | - | - | - |
$2,876
-
MMBtu
|
|
| 03 | 2.6211: Conserve energy by efficient use of vending machines | $1,317 | - |
$1,186
12,481
kWh
|
$131
-
kW-mo/yr
|
- | |
| 04 | 2.7124: Make a practice of turning off lights when not needed | $1,154 | - |
$1,154
8,127
kWh
|
- | - | |
| 05 | 2.7221: Lower temperature during the winter season and vice-versa | $811 | - |
$92
960
kWh
|
- |
$719
-
MMBtu
|
|
| 06 | 2.4322: Use or replace with energy efficient substitutes | $5,093 | $391 |
$4,249
44,725
kWh
|
$844
-
kW-mo/yr
|
- | |
| 07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $21,966 | $24,200 |
$17,852
187,916
kWh
|
$4,114
-
kW-mo/yr
|
- | |
| 08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,174 | $16,475 |
$10,990
115,679
kWh
|
$2,184
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $51,014 | $41,066 |
$39,131
407,863
kWh
|
$8,288
-
kW-mo/yr
|
$3,595
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $23,144 | $16,475 |
$16,938
174,262
kWh
|
$3,330
-
kW-mo/yr
|
$2,876
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs