Assessment Year | 2024 |
---|---|
Principal Product | Home Cleaning Products |
NAICS | 325612: Polish and Other Sanitation Good Manufacturing |
SIC | 2842: Specialty Cleaning, Polishing, and Sanitation Preparations |
Sales Range | $50 M to 100M |
# of Employees | 127 |
Plant Area |
120,000
ft2
|
Annual Production | 5,600,000
pieces
|
Production Hrs. Annual | 6,324
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $165,949 | 1,471,178 |
kWh
|
$0.11 | |
Electricity Fees | $559 | - |
|
- | |
Natural Gas | $24,298 | 2,876 |
MMBtu
|
$8.45 | |
Waste Disposal Costs | |||||
Water Usage | $86,684 | 11,188 |
Tgal
|
$7.75 | |
TOTAL YEARLY COSTS | $277,489 | ||||
RECOMMENDED SAVINGS* | $13,088 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,354 | $35 |
$2,354
20,872
kWh
|
- | |
02 | 2.6211: Conserve energy by efficient use of vending machines | $546 | - |
$546
4,836
kWh
|
- | |
03 | 2.7224: Reduce space conditioning during non-working hours | $1,767 | $448 |
$1,088
9,643
kWh
|
$679
-
MMBtu
|
|
04 | 2.2437: Recover waste heat from equipment | $3,831 | $1,865 |
$3,831
33,960
kWh
|
- | |
05 | 2.7135: Install occupancy sensors | $1,967 | $1,205 |
$1,967
17,437
kWh
|
- | |
06 | 2.2221: Use immersion heating in tanks, melting pots, etc | $1,077 | $1,105 |
$1,077
9,550
kWh
|
- | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,546 | $2,248 |
$1,546
13,702
kWh
|
- | |
TOTAL RECOMMENDED | $13,088 | $6,906 |
$12,409
110,001
kWh
|
$679
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs