Assessment Year | 2020 |
---|---|
Principal Product | Auto Components |
NAICS | 336370: Motor Vehicle Metal Stamping |
SIC | 3465: Automotive Stampings |
Sales Range | $100 M to 500M |
# of Employees | 950 |
Plant Area |
1,000,000
ft2
|
Annual Production | 66,255,116
units
|
Production Hrs. Annual | 4,400
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $2,736,094 | 58,743,772 |
kWh
|
$0.047 | |
Electricity Demand | $2,271,482 | 130,325 |
kW-mo/yr
|
$17.43 | |
Electricity Fees | $(-102,786.0) | - |
|
- | |
Natural Gas | $513,510 | 116,449 |
MMBtu
|
$4.41 | |
Waste Disposal Costs | |||||
Water Usage | $109,554 | 34,531 |
Tgal
|
$3.17 | |
TOTAL YEARLY COSTS | $5,527,854 | ||||
RECOMMENDED SAVINGS* | $90,482 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $11,541 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $2,249 | - |
$1,482
31,799
kWh
|
$767
-
kW-mo/yr
|
- | |
02 | 2.4322: Use or replace with energy efficient substitutes | $609 | - |
$400
8,585
kWh
|
$209
-
kW-mo/yr
|
- | |
03 | 2.7224: Reduce space conditioning during non-working hours | $64,260 | $1,554 |
$49,447
1,061,094
kWh
|
- |
$14,813
-
MMBtu
|
|
04 | 2.2437: Recover waste heat from equipment | $6,117 | $2,100 | - | - |
$6,117
-
MMBtu
|
|
05 | 2.7134: Use photocell controls | $184 | $138 |
$184
3,942
kWh
|
- | - | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $789 | $1,348 |
$388
8,316
kWh
|
$401
-
kW-mo/yr
|
- | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,777 | $4,138 |
$1,062
22,792
kWh
|
$715
-
kW-mo/yr
|
- | |
08 | 2.3413: Burn fossil fuel to produce steam to drive a steam turbine-generator and use steam exhaust for heat | $14,497 | $39,760 |
$7,176
154,000
kWh
|
$7,321
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $90,482 | $49,038 |
$60,139
1,290,528
kWh
|
$9,413
-
kW-mo/yr
|
$20,930
-
MMBtu
|
||
TOTAL IMPLEMENTED | $11,541 | $7,586 |
$3,332
71,492
kWh
|
$2,092
-
kW-mo/yr
|
$6,117
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs