Assessment Year | 2020 |
---|---|
Principal Product | Electrical Lighting Fixtures |
NAICS | 335122: Commercial, Industrial, and Institutional Electric Lighting Fixture Manufacturing |
SIC | 3351: Rolling, Drawing, and Extruding Of Copper |
Sales Range | $100 M to 500M |
# of Employees | 500 |
Plant Area |
300,000
ft2
|
Annual Production | 13,750,000
units
|
Production Hrs. Annual | 7,200
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $358,047 | 12,187,200 |
kWh
|
$0.029 | |
Electricity Demand | $631,335 | 25,314 |
kW-mo/yr
|
$24.94 | |
Electricity Fees | $4,080 | - |
|
- | |
Natural Gas | $270,939 | 66,897 |
MMBtu
|
$4.05 | |
Waste Disposal Costs | |||||
Water Usage | $144,018 | 38,749 |
Tgal
|
$3.72 | |
TOTAL YEARLY COSTS | $1,408,419 | ||||
RECOMMENDED SAVINGS* | $48,958 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $45,468 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4322: Use or replace with energy efficient substitutes | $672 | - |
$311
10,577
kWh
|
$361
-
kW-mo/yr
|
- | |
02 | 2.7221: Lower temperature during the winter season and vice-versa | $921 | - |
$192
6,532
kWh
|
- |
$729
-
MMBtu
|
|
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,490 | $131 |
$3,490
118,717
kWh
|
- | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,455 | $69 |
$1,455
49,473
kWh
|
- | - | |
05 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $12,685 | $10,860 |
$23,300
792,533
kWh
|
- |
$(-10,615.0)
-
MMBtu
|
|
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $27,563 | $32,451 |
$10,604
360,687
kWh
|
$16,959
-
kW-mo/yr
|
- | |
07 | 2.7232: Replace existing hvac unit with high efficiency model | $2,172 | $8,600 |
$476
16,200
kWh
|
$1,696
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $48,958 | $52,111 |
$39,828
1,354,719
kWh
|
$19,016
-
kW-mo/yr
|
$(-9,886.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | $45,468 | $51,980 |
$36,338
1,236,002
kWh
|
$19,016
-
kW-mo/yr
|
$(-9,886.0)
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs