Assessment Year | 2019 |
---|---|
Principal Product | Ice Cream and Milk |
NAICS | 311520: Ice Cream and Frozen Dessert Manufacturing |
SIC | 2024: Ice Cream and Frozen Desserts |
Sales Range | $100 M to 500M |
# of Employees | 400 |
Plant Area |
250,000
ft2
|
Annual Production | 277,059
ton
|
Production Hrs. Annual | 8,346
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,349,125 | 35,285,600 |
kWh
|
$0.038 |
Electricity Demand | $1,324,136 | 66,859 |
kW-mo/yr
|
$19.80 |
Electricity Fees | $(-51,364.0) | - |
|
- |
Natural Gas | $68,827 | 83,098 |
MMBtu
|
$0.83 |
TOTAL YEARLY COSTS | $2,690,724 | |||
RECOMMENDED SAVINGS* | $55,009 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $12,804 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7221: Lower temperature during the winter season and vice-versa | $547 | - |
$432
10,794
kWh
|
- | - |
$115
-
MMBtu
|
|
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,064 | $70 |
$3,549
88,715
kWh
|
$2,515
-
kW-mo/yr
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,236 | $208 |
$5,236
130,908
kWh
|
- | - | - | |
04 | 2.3212: Optimize plant power factor | $41,119 | $18,096 | - | - | $41,119 | - | |
05 | 2.7135: Install occupancy sensors | $539 | $348 |
$539
13,468
kWh
|
- | - | - | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $537 | $396 |
$314
7,845
kWh
|
$223
-
kW-mo/yr
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $967 | $1,966 |
$565
14,132
kWh
|
$402
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $55,009 | $21,084 |
$10,635
265,862
kWh
|
$3,140
-
kW-mo/yr
|
$41,119 |
$115
-
MMBtu
|
||
TOTAL IMPLEMENTED | $12,804 | $2,640 |
$9,664
241,600
kWh
|
$3,140
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs