| Assessment Year | 2019 |
|---|---|
| Principal Product | Cable assemblies and protective coatings |
| NAICS | 332813: Electroplating, Plating, Polishing, Anodizing, and Coloring |
| SIC | 3471: Electroplating, Plating, Polishing, Anodizing, and Coloring |
| Sales Range | $1 M to 5M |
| # of Employees | 18 |
| Plant Area |
32,000
ft2
|
| Annual Production | 700
units
|
| Production Hrs. Annual | 2,080
hrs
|
| Location (State) | Indiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $23,170 | 292,609 |
kWh
|
$0.079 | |
| Electricity Demand | $20,344 | 1,794 |
kW-mo/yr
|
$11.34 | |
| Electricity Fees | $8,050 | - |
|
- | |
| LPG | $13,380 | 989 |
MMBtu
|
$13.53 | |
| Other Gas | $8,000 | 250 |
MMBtu
|
$32.00 | |
| Waste Disposal Costs | |||||
| Water Usage | $666 | 10,000 |
Tgal
|
$0.067 | |
| Solid Waste (non-haz) | $15,270 | 10,000 |
lb
|
$1.53 | |
| TOTAL YEARLY COSTS | $88,879 | ||||
| RECOMMENDED SAVINGS* | $14,172 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $7,879 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | LPG Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.6212: Turn off equipment during breaks, reduce operating time | $286 | $7 |
$286
2,309
kWh
|
- | - | - | |
| 02 | 2.3512: De-energize excess transformer capacity | $248 | - |
$130
1,771
kWh
|
$118
-
kW-mo/yr
|
- | - | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $442 | $70 |
$442
6,046
kWh
|
- | - | - | |
| 04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $503 | $100 |
$503
6,876
kWh
|
- | - | - | |
| 05 | 2.7221: Lower temperature during the winter season and vice-versa | $1,980 | $440 |
$601
4,860
kWh
|
- | - |
$1,379
-
MMBtu
|
|
| 06 | 2.3212: Optimize plant power factor | $5,541 | $9,685 | - | - | $5,541 | - | |
| 07 | 2.2511: Insulate bare equipment | $96 | $200 | - | - | - |
$96
-
MMBtu
|
|
| 08 | 2.4322: Use or replace with energy efficient substitutes | $758 | $2,290 |
$758
6,126
kWh
|
- | - | - | |
| 09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,165 | $13,663 |
$3,946
34,526
kWh
|
$219
-
kW-mo/yr
|
- | - | |
| 10 | 2.2511: Insulate bare equipment | $153 | $692 | - | - | - |
$153
-
MMBtu
|
|
| TOTAL RECOMMENDED | $14,172 | $27,147 |
$6,666
62,514
kWh
|
$337
-
kW-mo/yr
|
$5,541 |
$1,628
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $7,879 | $16,470 |
$6,163
55,638
kWh
|
$337
-
kW-mo/yr
|
- |
$1,379
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | LPG Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs