Assessment Year | 2019 |
---|---|
Principal Product | Chemical Products |
NAICS | 325199: All Other Basic Organic Chemical Manufacturing |
SIC | 2899: Chemicals and Chemical Preparations, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 86 |
Plant Area |
120,000
ft2
|
Annual Production | 42,000,000
lb
|
Production Hrs. Annual | 4,905
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $61,054 | 1,291,820 |
kWh
|
$0.047 |
Electricity Demand | $49,496 | 2,771 |
kW-mo/yr
|
$17.86 |
Electricity Fees | $7,172 | - |
|
- |
Natural Gas | $84,472 | 14,274 |
MMBtu
|
$5.92 |
TOTAL YEARLY COSTS | $202,194 | |||
RECOMMENDED SAVINGS* | $29,585 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $8,230 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,409 | $5 |
$929
19,663
kWh
|
$480
-
kW-mo/yr
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $662 | $23 |
$662
13,998
kWh
|
- | - | - | |
03 | 2.7221: Lower temperature during the winter season and vice-versa | $1,721 | $260 |
$454
9,597
kWh
|
- | - |
$1,267
-
MMBtu
|
|
04 | 2.3212: Optimize plant power factor | $2,859 | $3,200 | - | - | $2,859 | - | |
05 | 2.4221: Install compressor air intakes in coolest locations | $252 | $476 |
$166
3,504
kWh
|
$86
-
kW-mo/yr
|
- | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,800 | $4,725 |
$1,433
30,320
kWh
|
$367
-
kW-mo/yr
|
- | - | |
07 | 2.2414: Use waste heat from hot flue gases to preheat | $3,037 | $11,000 | - | - | - |
$3,037
-
MMBtu
|
|
08 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $2,512 | $9,313 |
$1,305
27,622
kWh
|
$1,207
-
kW-mo/yr
|
- | - | |
09 | 2.1224: Replace boiler | $11,538 | $50,526 | - | - | - |
$11,538
-
MMBtu
|
|
10 | 2.4322: Use or replace with energy efficient substitutes | $3,795 | $17,400 | - | - | - |
$3,795
-
MMBtu
|
|
TOTAL RECOMMENDED | $29,585 | $96,928 |
$4,949
104,704
kWh
|
$2,140
-
kW-mo/yr
|
$2,859 |
$19,637
-
MMBtu
|
||
TOTAL IMPLEMENTED | $8,230 | $22,884 |
$2,715
57,419
kWh
|
$453
-
kW-mo/yr
|
- |
$5,062
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs