| Assessment Year | 2019 |
|---|---|
| Principal Product | Potable Drinking Water |
| NAICS | 221310: Water Supply and Irrigation Systems |
| SIC | 4941: Water Supply |
| Sales Range | $10 M to 50M |
| # of Employees | 6 |
| Plant Area |
1,540,170
ft2
|
| Annual Production | 5,794,000
Tgal
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Indiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $680,712 | 9,560,242 |
kWh
|
$0.071 |
| Electricity Demand | $56,317 | 22,313 |
kW-mo/yr
|
$2.52 |
| Electricity Fees | $669 | - |
|
- |
| Natural Gas | $16,476 | 2,143 |
MMBtu
|
$7.69 |
| TOTAL YEARLY COSTS | $754,174 | |||
| RECOMMENDED SAVINGS* | $130,128 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $124,562 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7221: Lower temperature during the winter season and vice-versa | $308 | - | - | - |
$308
-
MMBtu
|
|
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,151 | $23 |
$5,151
54,283
kWh
|
- | - | |
| 03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $415 | $680 |
$415
4,375
kWh
|
- | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,878 | $14,599 |
$6,648
88,427
kWh
|
$230
-
kW-mo/yr
|
- | |
| 05 | 2.9114: Use solar heat to make electricty | $117,376 | $1,431,096 |
$117,376
1,566,266
kWh
|
- | - | |
| TOTAL RECOMMENDED | $130,128 | $1,446,398 |
$129,590
1,713,351
kWh
|
$230
-
kW-mo/yr
|
$308
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $124,562 | $1,445,695 |
$124,024
1,654,693
kWh
|
$230
-
kW-mo/yr
|
$308
-
MMBtu
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs