Assessment Year | 2018 |
---|---|
Principal Product | PVD Wheels |
NAICS | 332812: Metal Coating, Engraving (except Jewelry and Silverware), and Allied Services to Manufacturers |
SIC | 3479: Coating, Engraving, and Allied Services, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 75 |
Plant Area |
188,500
ft2
|
Annual Production | 260,000
pieces
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $450,511 | 6,615,000 |
kWh
|
$0.068 |
Electricity Demand | $153,685 | 15,584 |
kW-mo/yr
|
$9.86 |
Electricity Fees | $10,155 | - |
|
- |
Natural Gas | $194,434 | 38,665 |
MMBtu
|
$5.03 |
TOTAL YEARLY COSTS | $808,785 | |||
RECOMMENDED SAVINGS* | $88,064 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $73,222 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $23,973 | $5 |
$18,589
272,964
kWh
|
$5,384
-
kW-mo/yr
|
- | |
02 | 2.7224: Reduce space conditioning during non-working hours | $756 | - |
$253
3,721
kWh
|
- |
$503
-
MMBtu
|
|
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,835 | $130 |
$4,835
71,003
kWh
|
- | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,072 | $30 |
$1,072
15,737
kWh
|
- | - | |
05 | 2.7134: Use photocell controls | $403 | $35 |
$403
5,922
kWh
|
- | - | |
06 | 2.7135: Install occupancy sensors | $21,079 | $3,360 |
$21,079
309,523
kWh
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,905 | $5,340 |
$3,027
44,453
kWh
|
$878
-
kW-mo/yr
|
- | |
08 | 2.7241: Install outside air damper / economizer on hvac unit | $13,014 | $13,520 |
$13,014
191,097
kWh
|
- | - | |
09 | 2.2511: Insulate bare equipment | $674 | $945 | - | - |
$674
-
MMBtu
|
|
10 | 2.4221: Install compressor air intakes in coolest locations | $11,070 | $21,274 |
$8,585
126,060
kWh
|
$2,485
-
kW-mo/yr
|
- | |
11 | 2.2414: Use waste heat from hot flue gases to preheat | $7,283 | $30,250 | - | - |
$7,283
-
MMBtu
|
|
TOTAL RECOMMENDED | $88,064 | $74,889 |
$70,857
1,040,480
kWh
|
$8,747
-
kW-mo/yr
|
$8,460
-
MMBtu
|
||
TOTAL IMPLEMENTED | $73,222 | $61,339 |
$56,518
829,925
kWh
|
$8,747
-
kW-mo/yr
|
$7,957
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs