| Assessment Year | 2018 |
|---|---|
| Principal Product | fiberglass backing |
| NAICS | 326199: All Other Plastics Product Manufacturing |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $50 M to 100M |
| # of Employees | 93 |
| Plant Area |
468,000
ft2
|
| Annual Production | 97,734,287
units
|
| Production Hrs. Annual | 8,616
hrs
|
| Location (State) | Illinois |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,300,701 | 28,800,595 |
kWh
|
$0.045 |
| Electricity Demand | $90,049 | 44,585 |
kW-mo/yr
|
$2.02 |
| Electricity Fees | $117,692 | - |
|
- |
| Natural Gas | $1,973,929 | 598,559 |
MMBtu
|
$3.30 |
| TOTAL YEARLY COSTS | $3,482,371 | |||
| RECOMMENDED SAVINGS* | $12,974 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $5,707 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7224: Reduce space conditioning during non-working hours | $4,724 | - |
$2,414
53,644
kWh
|
- |
$2,310
-
MMBtu
|
|
| 02 | 2.7135: Install occupancy sensors | $548 | $1,325 |
$548
12,187
kWh
|
- | - | |
| 03 | 2.2437: Recover waste heat from equipment | $2,543 | $9,687 |
$(-549.6)
(-12,212)
kWh
|
$(-37.8)
-
kW-mo/yr
|
$3,130
-
MMBtu
|
|
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,159 | $21,897 |
$4,595
102,119
kWh
|
$564
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $12,974 | $32,909 |
$7,008
155,738
kWh
|
$526
-
kW-mo/yr
|
$5,440
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $5,707 | $23,222 |
$5,143
114,306
kWh
|
$564
-
kW-mo/yr
|
- | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs