| Assessment Year | 2018 |
|---|---|
| Principal Product | Adhesive |
| NAICS | 325520: Adhesive Manufacturing |
| SIC | 2891: Adhesives and Sealants |
| Sales Range | $10 M to 50M |
| # of Employees | 109 |
| Plant Area |
120,000
ft2
|
| Annual Production | 19,798,914
pieces
|
| Production Hrs. Annual | 4,368
hrs
|
| Location (State) | Indiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $212,070 | 3,386,222 |
kWh
|
$0.063 | |
| Electricity Demand | $102,767 | 9,322 |
kW-mo/yr
|
$11.02 | |
| Electricity Fees | $2,443 | - |
|
- | |
| Natural Gas | $25,269 | 4,239 |
MMBtu
|
$5.96 | |
| Waste Disposal Costs | |||||
| Water Usage | $4,874 | 302,733 |
Tgal
|
$0.016 | |
| Water Disposal | $14,496 | 1,203 |
Tgal
|
$12.05 | |
| TOTAL YEARLY COSTS | $361,919 | ||||
| RECOMMENDED SAVINGS* | $56,926 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $22,199 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7221: Lower temperature during the winter season and vice-versa | $3,602 | $25 |
$1,132
18,246
kWh
|
- | - |
$2,470
-
MMBtu
|
- | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,685 | $275 |
$7,124
114,863
kWh
|
$3,561
-
kW-mo/yr
|
- | - | - | |
| 03 | 3.4116: Meter recycled water (to reduce sewer charges) | $3,492 | $600 | - | - | - | - |
$3,492
-
Tgal
|
|
| 04 | 2.3212: Optimize plant power factor | $7,330 | $4,122 | - | - | $7,330 | - | - | |
| 05 | 4.812: Apply for investment incentives | $161 | $100 | - | - | $161 | - | - | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $183 | $639 |
$121
1,102
kWh
|
$62
-
kW-mo/yr
|
- | - | - | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,259 | $15,632 |
$2,828
45,602
kWh
|
$1,431
-
kW-mo/yr
|
- | - | - | |
| 08 | 2.4322: Use or replace with energy efficient substitutes | $25,428 | $6,125 |
$16,961
273,480
kWh
|
$8,467
-
kW-mo/yr
|
- | - | - | |
| 09 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $1,786 | $1,576 |
$1,027
9,360
kWh
|
$529
-
kW-mo/yr
|
- |
$230
-
MMBtu
|
- | |
| TOTAL RECOMMENDED | $56,926 | $29,094 |
$29,193
462,653
kWh
|
$14,050
-
kW-mo/yr
|
$7,491 |
$2,700
-
MMBtu
|
$3,492
-
Tgal
|
||
| TOTAL IMPLEMENTED | $22,199 | $16,632 |
$11,084
178,711
kWh
|
$4,992
-
kW-mo/yr
|
$161 |
$2,470
-
MMBtu
|
$3,492
-
Tgal
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs