Assessment Year | 2017 |
---|---|
Principal Product | Fulfillment Center |
NAICS | 493110: General Warehousing and Storage |
SIC | 4225: General Warehousing and Storage |
Sales Range | $10 M to 50M |
# of Employees | 375 |
Plant Area |
748,000
ft2
|
Annual Production | 64,000,000
units
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $252,595 | 5,456,250 |
kWh
|
$0.046 |
Electricity Demand | $192,716 | 11,349 |
kW-mo/yr
|
$16.98 |
Electricity Fees | $17,103 | - |
|
- |
Natural Gas | $100,100 | 17,329 |
MMBtu
|
$5.78 |
TOTAL YEARLY COSTS | $562,514 | |||
RECOMMENDED SAVINGS* | $80,038 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $77,021 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7221: Lower temperature during the winter season and vice-versa | $21,777 | $64 |
$3,767
81,386
kWh
|
- |
$18,010
-
MMBtu
|
|
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,005 | $11 |
$1,033
22,310
kWh
|
$972
-
kW-mo/yr
|
- | |
03 | 2.6211: Conserve energy by efficient use of vending machines | $714 | - |
$475
10,271
kWh
|
$239
-
kW-mo/yr
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $40,350 | $48,658 |
$22,380
483,465
kWh
|
$17,970
-
kW-mo/yr
|
- | |
05 | 2.7241: Install outside air damper / economizer on hvac unit | $4,833 | $11,638 |
$4,833
104,413
kWh
|
- | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $42 | $84 |
$28
613
kWh
|
$14
-
kW-mo/yr
|
- | |
07 | 2.6218: Turn off equipment when not in use | $298 | $1,465 |
$298
6,445
kWh
|
- | - | |
08 | 2.2622: Replace existing chiller with high efficiency model | $10,019 | $47,182 |
$955
20,641
kWh
|
$944
-
kW-mo/yr
|
$8,120
-
MMBtu
|
|
TOTAL RECOMMENDED | $80,038 | $109,102 |
$33,769
729,544
kWh
|
$20,139
-
kW-mo/yr
|
$26,130
-
MMBtu
|
||
TOTAL IMPLEMENTED | $77,021 | $107,626 |
$31,963
690,518
kWh
|
$18,928
-
kW-mo/yr
|
$26,130
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs