Assessment Year | 2017 |
---|---|
Principal Product | Refined Soybean Oil and Meal |
NAICS | 311225: Fats and Oils Refining and Blending |
SIC | 2075: Soybean Oil Mills |
Sales Range | greater than $500 M |
# of Employees | 113 |
Plant Area |
5,096,520
ft2
|
Annual Production | 700,000,000
lb
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $3,031,000 | 62,225,622 |
kWh
|
$0.049 | |
Electricity Demand | $1,154,068 | 100,704 |
kW-mo/yr
|
$11.46 | |
Electricity Fees | $46,249 | - |
|
- | |
Natural Gas | $3,423,261 | 1,173,415 |
MMBtu
|
$2.92 | |
Waste Disposal Costs | |||||
Water Usage | $153,345 | 129,827,800 |
Tgal
|
$0.001 | |
Water Disposal | $338,922 | 59,669 |
Tgal
|
$5.68 | |
TOTAL YEARLY COSTS | $8,146,845 | ||||
RECOMMENDED SAVINGS* | $677,041 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $63,752 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.6211: Conserve energy by efficient use of vending machines | $1,035 | - |
$783
16,031
kWh
|
$252
-
kW-mo/yr
|
- | - | |
02 | 2.7221: Lower temperature during the winter season and vice-versa | $23,755 | $72 |
$11,850
242,822
kWh
|
- |
$11,905
-
MMBtu
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,755 | $189 |
$1,314
26,929
kWh
|
$441
-
kW-mo/yr
|
- | - | |
04 | 2.7135: Install occupancy sensors | $3,851 | $308 |
$3,851
78,909
kWh
|
- | - | - | |
05 | 2.1233: Analyze flue gas for proper air/fuel ratio | $5,139 | $432 | - | - |
$5,139
-
MMBtu
|
- | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $21,213 | $2,430 |
$15,884
325,500
kWh
|
$5,329
-
kW-mo/yr
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,313 | $7,280 |
$9,969
204,288
kWh
|
$3,344
-
kW-mo/yr
|
- | - | |
08 | 2.7241: Install outside air damper / economizer on hvac unit | $509 | $529 |
$509
10,430
kWh
|
- | - | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $332 | $798 |
$251
5,151
kWh
|
$81
-
kW-mo/yr
|
- | - | |
10 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $606,139 | $2,150,000 |
$798,550
16,363,740
kWh
|
$267,456
-
kW-mo/yr
|
$86,829
-
MMBtu
|
$(-546,696.0) | |
TOTAL RECOMMENDED | $677,041 | $2,162,038 |
$842,961
17,273,800
kWh
|
$276,903
-
kW-mo/yr
|
$103,873
-
MMBtu
|
$(-546,696.0) | ||
TOTAL IMPLEMENTED | $63,752 | $11,012 |
$37,954
777,761
kWh
|
$8,754
-
kW-mo/yr
|
$17,044
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs