| Assessment Year | 2016 |
|---|---|
| Principal Product | Anodized Aluminum |
| NAICS | 332813: Electroplating, Plating, Polishing, Anodizing, and Coloring |
| SIC | 3471: Electroplating, Plating, Polishing, Anodizing, and Coloring |
| Sales Range | $1 M to 5M |
| # of Employees | 38 |
| Plant Area |
28,000
ft2
|
| Annual Production | 3,207,459
pieces
|
| Production Hrs. Annual | 6,000
hrs
|
| Location (State) | Indiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $61,873 | 1,068,600 |
kWh
|
$0.058 |
| Electricity Demand | $33,264 | 3,153 |
kW-mo/yr
|
$10.55 |
| Electricity Fees | $1,678 | - |
|
- |
| Natural Gas | $100,626 | 18,555 |
MMBtu
|
$5.42 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $8,094 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $3,725 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7221: Lower temperature during the winter season and vice-versa | $759 | $4 | - | - | - |
$759
-
MMBtu
|
|
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $688 | $5 |
$504
8,700
kWh
|
$184
-
kW-mo/yr
|
- | - | |
| 03 | 2.4322: Use or replace with energy efficient substitutes | $720 | $38 |
$720
12,433
kWh
|
- | - | - | |
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $491 | $159 |
$360
6,222
kWh
|
$131
-
kW-mo/yr
|
- | - | |
| 05 | 2.7135: Install occupancy sensors | $500 | $285 |
$500
8,640
kWh
|
- | - | - | |
| 06 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $136 | $82 | - | - | - |
$136
-
MMBtu
|
|
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,287 | $5,648 |
$943
16,285
kWh
|
$344
-
kW-mo/yr
|
- | - | |
| 08 | 2.3212: Optimize plant power factor | $3,317 | $10,850 | - | - | $3,317 | - | |
| 09 | 2.4221: Install compressor air intakes in coolest locations | $196 | $940 |
$144
2,485
kWh
|
$52
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $8,094 | $18,011 |
$3,171
54,765
kWh
|
$711
-
kW-mo/yr
|
$3,317 |
$895
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $3,725 | $6,101 |
$2,307
39,847
kWh
|
$659
-
kW-mo/yr
|
- |
$759
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs