Assessment Year | 2016 |
---|---|
Principal Product | Reusable steel racks for automotive parts |
NAICS | 332999: All Other Miscellaneous Fabricated Metal Product Manufacturing |
SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 90 |
Plant Area |
85,000
ft2
|
Annual Production | 7,000
pieces
|
Production Hrs. Annual | 2,383
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $34,316 | 364,880 |
kWh
|
$0.094 |
Electricity Fees | $3,005 | - |
|
- |
Natural Gas | $12,053 | 1,439 |
MMBtu
|
$8.38 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $6,266 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,376 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,353 | $58 |
$1,353
15,068
kWh
|
- | - | |
02 | 2.7221: Lower temperature during the winter season and vice-versa | $1,602 | $99 |
$1,217
14,032
kWh
|
- |
$385
-
MMBtu
|
|
03 | 2.4322: Use or replace with energy efficient substitutes | $76 | $62 |
$76
872
kWh
|
- | - | |
04 | 4.812: Apply for investment incentives | $1,633 | $2,000 | - | $1,633 | - | |
05 | 2.7135: Install occupancy sensors | $1,345 | $3,616 |
$1,345
13,942
kWh
|
- | - | |
06 | 2.2511: Insulate bare equipment | $257 | $776 | - | - |
$257
-
MMBtu
|
|
TOTAL RECOMMENDED | $6,266 | $6,611 |
$3,991
43,914
kWh
|
$1,633 |
$642
-
MMBtu
|
||
TOTAL IMPLEMENTED | $4,376 | $3,835 |
$3,991
43,914
kWh
|
- |
$385
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs