Assessment Year | 2013 |
---|---|
Principal Product | clay coated recycled paperboard |
NAICS | 322130: Paperboard Mills |
SIC | 2621: Paper Mills |
Sales Range | $50 M to 100M |
# of Employees | 194 |
Plant Area |
470,000
ft2
|
Annual Production | 137,000
ton
|
Production Hrs. Annual | 8,640
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,619,673 | 101,840,657 |
kWh
|
$0.016 |
Electricity Demand | $1,742,920 | 160,935 |
kW-mo/yr
|
$10.83 |
Electricity Fees | $2,972,292 | - |
|
- |
Natural Gas | $3,279,791 | 995,590 |
MMBtu
|
$3.29 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $267,615 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $216,518 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 4.812: Apply for investment incentives | $42,227 | - | - | - | - | $42,227 | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $109,212 | - |
$64,974
1,866,240
kWh
|
$44,238
-
kW-mo/yr
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,467 | $430 |
$1,468
42,163
kWh
|
$999
-
kW-mo/yr
|
- | - | |
04 | 2.7135: Install occupancy sensors | $734 | $100 |
$734
21,082
kWh
|
- | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,545 | $1,400 |
$7,545
216,709
kWh
|
- | - | - | |
06 | 2.2511: Insulate bare equipment | $5,669 | $2,019 | - | - |
$5,669
-
MMBtu
|
- | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $99,761 | $59,384 |
$54,295
1,559,520
kWh
|
$45,466
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $267,615 | $63,333 |
$129,016
3,705,714
kWh
|
$90,703
-
kW-mo/yr
|
$5,669
-
MMBtu
|
$42,227 | ||
TOTAL IMPLEMENTED | $216,518 | $60,784 |
$126,814
3,642,469
kWh
|
$89,704
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs