Assessment Year | 2013 |
---|---|
Principal Product | Fuel System Components |
NAICS | 332999: All Other Miscellaneous Fabricated Metal Product Manufacturing |
SIC | 3536: Overhead Traveling Cranes, Hoists, and Monorail Systems |
Sales Range | $10 M to 50M |
# of Employees | 125 |
Plant Area |
125,000
ft2
|
Annual Production | 15,000,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $273,797 | 5,456,400 |
kWh
|
$0.050 |
Electricity Demand | $154,403 | 14,001 |
kW-mo/yr
|
$11.03 |
Natural Gas | $41,957 | 7,496 |
MMBtu
|
$5.60 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $62,919 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $43,542 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Other Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $1,644 | - |
$1,644
36,060
kWh
|
- | - | - | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $5,757 | - |
$4,501
86,899
kWh
|
$1,256
-
kW-mo/yr
|
- | - | |
03 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $730 | - |
$730
16,000
kWh
|
- | - | - | |
04 | 2.7135: Install occupancy sensors | $1,044 | $118 |
$1,044
22,895
kWh
|
- | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $24,010 | $1,400 |
$24,010
463,518
kWh
|
- | - | - | |
06 | 2.2511: Insulate bare equipment | $7,093 | $380 | - | - | - |
$7,093
-
MMBtu
|
|
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,795 | $8,625 |
$8,440
162,936
kWh
|
$2,355
-
kW-mo/yr
|
- | - | |
08 | 2.3212: Optimize plant power factor | $10,702 | $17,052 | - | - | $10,702 | - | |
09 | 2.7241: Install outside air damper / economizer on hvac unit | $1,144 | $3,702 |
$1,144
25,101
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $62,919 | $31,277 |
$41,513
813,409
kWh
|
$3,611
-
kW-mo/yr
|
$10,702 |
$7,093
-
MMBtu
|
||
TOTAL IMPLEMENTED | $43,542 | $10,405 |
$34,094
662,514
kWh
|
$2,355
-
kW-mo/yr
|
- |
$7,093
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Other Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs