| Assessment Year | 2026 |
|---|---|
| Principal Product | Office Space |
| NAICS | 551114: Corporate, Subsidiary, and Regional Managing Offices |
| SIC | 6541: Title Abstract Offices |
| Sales Range | less than $500 k |
| # of Employees | 100 |
| Plant Area |
50,243
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 2,860
hrs
|
| Location (State) | Illinois |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $43,783 | 440,928 |
kWh
|
$0.099 |
| Electricity Demand | $19,273 | 1,545 |
kW-mo/yr
|
$12.47 |
| Electricity Fees | $5,191 | - |
|
- |
| Natural Gas | $2,564 | 857 |
MMBtu
|
$2.99 |
| Other Energy | $1,035 | 1 |
MMBtu
|
$1,035.00 |
| TOTAL YEARLY COSTS | $71,846 | |||
| RECOMMENDED SAVINGS* | $36,831 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7221: Lower temperature during the winter season and vice-versa | $11,793 | - |
$11,347
113,467
kWh
|
$446
-
kW-mo/yr
|
- | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,208 | $18,739 |
$4,272
42,725
kWh
|
$1,182
-
kW-mo/yr
|
$(-273.4)
-
MMBtu
|
$2,027 | |
| 03 | 2.7135: Install occupancy sensors | $2,178 | $8,225 |
$1,032
10,323
kWh
|
$1,145
-
kW-mo/yr
|
- | - | |
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $11,604 | $17,739 |
$9,868
98,680
kWh
|
$2,086
-
kW-mo/yr
|
- | $(-350.0) | |
| 05 | 2.2625: Chill water to the highest temperature possible | $3,509 | - |
$2,889
28,886
kWh
|
$620
-
kW-mo/yr
|
- | - | |
| 06 | 2.6226: Optimize filtration cleaning / replacement to minimize air resistance | $539 | $74 |
$234
2,340
kWh
|
$306
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $36,831 | $44,777 |
$29,642
296,421
kWh
|
$5,785
-
kW-mo/yr
|
$(-273.4)
-
MMBtu
|
$1,677 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs