| Assessment Year | 2026 |
|---|---|
| Principal Product | Food Packaging |
| NAICS | 322212: Folding Paperboard Box Manufacturing |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $100 M to 500M |
| # of Employees | 400 |
| Plant Area |
450,000
ft2
|
| Annual Production | 44,000,000
lb
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Illinois |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $794,148 | 11,829,593 |
kWh
|
$0.067 |
| Electricity Demand | $375,294 | 24,215 |
kW-mo/yr
|
$15.50 |
| Electricity Fees | $132,189 | - |
|
- |
| Natural Gas | $430,066 | 51,798 |
MMBtu
|
$8.30 |
| Other Gas | $65,346 | 1 |
MMBtu
|
$65,346.00 |
| TOTAL YEARLY COSTS | $1,797,043 | |||
| RECOMMENDED SAVINGS* | $61,062 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4239: Eliminate or reduce compressed air usage | $4,722 | $1,338 |
$2,341
34,944
kWh
|
$2,381
-
kW-mo/yr
|
- | |
| 02 | 2.2437: Recover waste heat from equipment | $1,362 | $2,900 | - | - |
$1,362
-
MMBtu
|
|
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,117 | $5,000 |
$4,645
69,331
kWh
|
$1,472
-
kW-mo/yr
|
- | |
| 04 | 2.6218: Turn off equipment when not in use | $18,089 | $6,484 |
$10,276
153,378
kWh
|
$7,813
-
kW-mo/yr
|
- | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,677 | $720 |
$1,338
19,973
kWh
|
$339
-
kW-mo/yr
|
- | |
| 06 | 2.1243: Use heat from boiler blowdown to preheat boiler feed water | $6,218 | $10,544 | - | - |
$6,218
-
MMBtu
|
|
| 07 | 2.3191: Use demand controller or load shedder | $819 | $1,912 |
$387
5,780
kWh
|
- |
$432
-
MMBtu
|
|
| 08 | 2.4239: Eliminate or reduce compressed air usage | $709 | $2,496 |
$491
7,321
kWh
|
$218
-
kW-mo/yr
|
- | |
| 09 | 2.2427: Use waste heat from hot flue gases to preheat incoming fluids | $6,608 | $10,990 | - | - |
$6,608
-
MMBtu
|
|
| 10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,563 | $1,775 |
$2,687
40,104
kWh
|
$876
-
kW-mo/yr
|
- | |
| 11 | 2.2136: Install / repair insulation on steam lines | $11,178 | $2,752 | - | - |
$11,178
-
MMBtu
|
|
| TOTAL RECOMMENDED | $61,062 | $46,911 |
$22,166
330,831
kWh
|
$13,098
-
kW-mo/yr
|
$25,798
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs